The configuration of the panel like intrusion detection zone’ s and area’ s should be done locally in the intrusion panel.
Note! The settings below must correspond with the settings in iProtect.
2.2 Settings in the UNii intrusion panel
...
Go to IP settings and enter the following settings:
Generic interface menu:
Type (Encryption): Full encryption
Local port: 6502
Transport protocol: UDP
Input update interval (s): 3
Encryption key: as desired
API Version: UNii APISave and send this data to the intrusion panel
Note! These settings must correspond with the settings in iProtect.
2.3 Unii Programming manual
...
Normally alarm groups are added automatically when the read-in button is pressed. If desired it is also possible to add alarmgroups alarm groups manually.
Right-click on the General intrusion node that just is made and select add alarm group
Enter the following data:
Name: Enter a logical name (same name as the intrusion area in the panel)
No. at the line: The number of the intrusion area
Alarm group mode: Select ‘Disarm’
Point changes when group off: Select a time zone (example: Office)
< In other words, during which time zone must iProtect monitor the alarm points
for e.g. displaying these statuses on the Keymap™>
Write point events to database: Select a time zone (example: Office)
< In other words, during which time zone must iProtect register the alarm points
for e.g. logging these statuses as event and triggering procedures>Save the record
...
Open the Alarm group that just is made and right click on Alarm point list, select add alarm point.
Enter the following data:
Name: Enter a logical name (same name as the intrusion zone in the panel)
Omit: ‘off’
Addr. No.: The number of the intrusion zone.Enter Save the record.
...
5
...
Visualization in Keymap
5.1 Placing Widgets for visualization and control
...