Installation Manual | TM-xxxxxxx-AVW-01

iProtect Access / Security | Functionalities |Deister TSU200 reader with SIC 6347

Image Modified

This manual represents the knowledge at the above-mentioned time. TKH security works non-stop to improve her products. For the most recent technical information please contact your consultant or dealer.

...

This article explains how you can implement the Voxio-T-1570-Z reader deister reader TSU 200 with SIC 6347 based on OSDP communication and describes the functions and settings.

...

SIC connector

Signal

CAT5 cable > Orion PRT 1 or 2

Pin 13

VCC 8-30V DC

Pin 2

GND

Pin 310

B

White/Orange & White/Green

Pin 49

A

Orange&Green

...

Info

Max. cable distance between Orion and the PHG SIC reader = 30 120 Mtr. This is based on CAT5E - 24AWG

Info

This cable distance is based without with installing an external power supply. (for Reader and Sic)

5. Implementation

5.1 General

...

  1. Connect the reader (see chapter “Connecting the reader”)

  2. Press the discover button in the line dialog of the Pluto.

  3. Wait until the discover process is ready: Read-in event=> Read-in event: Stop, Line: xxx…

  4. Refresh the line dialog of the Pluto, if an OSDP device is detected it will be shown as a Node below the Port of the Orion where the reader is connected to.

  5. Change the OSDP compatibility setting at the OSDP node to “No No reader in capabilities”capabilities
    (Not full compliant with OSDP Deister SIC 6347)

  6. Right mouse click at the OSDP reader in the treeview and click on “add reader”

    • Fill in the logic unique name of the reader.

    • Click on the save button.

Info

If an rs485 RS485 reader has already been connected to the PRT port, the pluto must first be restarted before the discover is executed and the OSDP node can be created.

The discover function for OSDP devices checks for the following settings:
Baudrate:                    9600, 19K2, 115K2  baud,  They are all non-parity, 8 bit, 1 stop bit
Device address:          0, 1, 2, 3, 4, 5, 6, 7, 8, 13, 14, 24

If other settings are necessary, set these settings manually.

Note: SIC 6347 default: 9600N81 baud, OSDP address 1

5.3 OSDP reader settings

For OSDP readers there are some specific settings.

...

Buzzer time | card recognized

Setting

Behavior

Empty

No buzzer when card is recognized

1 - 15 (for Deister keep empty !)

buzzer time (1/10 sec), empty is no buzzer

Info

Most used setting for buzzer time = 2

5.4 Keypad buttons

...

Keypad

...

Description

...

0-9

...

Numeric numbers

...

C

...

On keypad is used as restore key to re-enter the PIN on the pending access request.

...

E

...

On keypad is used for reset pincode (do not use as pincode only key).

By reset pincode when using the pincode only function an reader error event occurs, with Error description: “Error: Wrong numbers of characters received”

The Voxio-T-1570-Z reader can be used in three different access modes, depending on the authentication mode setting on the reader and the card data interpretation setting of the cards being used.

The reader authentication method can be set at the general tab on the reader detail page.

...

Mode

...

Reader authentication method

...

How to link

...

Card only

...

Not required

...

*Assign cards to people - Knowledge Base - Confluence (atlassian.net)

...

Card+Pincode

...

Pincode required

...

*Assign cards to people - Knowledge Base - Confluence (atlassian.net)

...

Card / Pincode only

...

Not required

...

Not supported by Deister, if selected the buzzer will start but does not stop. Reboot needed to solve this.

6. Secure channel

OSDP v2 with Secure Channel has AES-128 encryption to ensure that communication between the targeted devices is strict and secure.

...

Note

Once a key is set into the reader it cannot be cleared or rewritten by the system (not allowed in the OSDP protocol, security risk). If the key must be cleared (Reset) follow the procedure what is delivered by the reader manufacturer.

7. iProtect settings SIC 6347

Card data presentation

Format

Decimal

Calculated length

7

Card data interpretation

Format

Reader communication protocol

ABA

Card type

None

Data length

28

System code

Start

1

Code

“empty“

facility

Start

1

Code

“empty“

Card number

Start

22

Length

7

Modulo

“empty“

Offset

“empty“