Installation Manual | IM-20210309-TP-45

Access Control | Controllers | Polyx™ Controllers |

View file
nameIM-20210309-TP-46.pdf

Table of Contents

This manual represents the knowledge at the above-mentioned time. TKH security works non-stop to improve her products. For the most recent technical information please contact your consultant or dealer.

Table of content

...


...

1 Product description

Polyx™ is a platform with several possible functions. It is safer, more robust and variable than the competing platform Orbit.

...

Encryption
The communication between Polyx™ and iPU-8 is encrypted (AES 256-bit encryption). The access to Polyx™ is secured with a login and a password. Therefore Polyx™ is optimally protected against any influences from outside.

Note! Using higher security levels can effect the reading time of the cards.

...

2 Planning

Make a plan, how and where Polyx™ and the other devices have to be connected.

...

2.2.1 Polyx™ D+ control

...

2.2.2 Polyx™ ND+ control

  1. Image Modified

...

3 Mounting

  • Mount the rail against the wall (mounting rail 35 mm, see NEN-EN 50022).

  • Push Polyx™ against the rail and click it in.

...

  • Connect the readers, I/O’s, ethernet connections and possibly the power supply, power supply for the door lock, Orbits etc.

4.1 Ports

...

  1. Separate power supply 24VDC; 2) Emergency power supply 12VDC (battery);

  2. Ethernet connection including power supply (PoE+: tot 30W);

  3. Serial RS 232 port (diagnostics/monitor);

  4. 2 serial RS422 ports for readers, reader-Orbits, I/O-Orbits;

  5. RS232 (external connection);

  6. 12 inputs/outputs;

  7. power supply for the door lock 12VDC (not available if power supply=PoE)

4.2 Separate power supply 24VDC

...

Even if you do have a power supply via PoE+ you might decide to have a separate power supply as a back-up system.
The power supply connection is robust against wrong connecting of the connection wires.

Galvanic separation:

Attention! Always execute the separate power supply of the Polyx galvanically separated if separate power supply and PoE/PoE+ are used!
Use a transformator between power supply (primary circuit) and the Polyx (secondary circuit)!
Polyx devices without galvanic separation are not CE-compliant!

If separate power supply Polyx AND separate supply door lock:

...

Attention! If a separate power supply of the Polyx (A) and for the door lock is being used, you have to connect GND of the I/O section with – of the 24VDC supply (B) and with – of the separate door lock supply(C).

4.3 Emergency battery 12VDC

...

  • Sirius and Polyx are mounted in different buildings and therefore the connection cable leaves the building or

  • an existing cable to a previously mounted card reader is used or

  • an overvoltage security for the reader is needed or

  • an external power supply for the card reader Sirius is needed.

Note! If one of the stated conditions applies, you have to connect an adapterboard between
Sirius and Polyx!

Polyx and the card reader Sirius are connected by a default UTP cable.
At the Polyx side the connection is done by a RJ45 plug.
The wires of the RJ45 connector are standardized in EIA-568-B.

...

  • Check the data and press any button.

  • Enter “3” (Goto main menu)

  • Enter “r” (Restart system)

Attention! Do NOT restart by removing the voltage of the Polyx! Otherwise the Polyx will be damaged!

...

6 Loading firmware

6.1 Loading new firmware

...

You can assign a card group of emergency cards to the Polyx under “node”, if it controls card readers. This card group has access, when Polyx™ stands in emergency mode.

Note! The maximum for emergency cards per node is 64 in iProtect™!

...

8 Trouble shooting

8.1 Situation

...

  • Enter ‘kflipo’ and press Enter. All flash banks will be deleted.
    Will now erase 0xFB8000 bytes starting from 0x40000
    ……….
    Flash Erase complete. 0xFC0000 bytes erased
    done...

  • Enter ‘dlnipo’ and press Enter. The software will now be loaded now from the laptop or
    PC with the “Tftpd32” program.
    Trying to download FS fs.s19
    Downloading S-Record 'fs.s19' from 192.168.0.244
    S-record download successful!
    TFTP transfer completed
    Read 1897316 bytes (3706 blocks)
    Trying to download SquashFS squashfs.img
    downloading to address: 0x40EA11B9
    Downloading Image 'squashfs.img' from 192.168.0.244
    TFTP Error #1: File not found
    Errors in TFTP download.
    ......
    Flash Erase complete. 0xC0000 bytes erased
    kernel Programming complete
    board will autostart from flash

  • The error message TFTP Error #1 is no problem, in the script an extra file will be looked for, but this is of no importance.

  • Enter ‘gfl’ and press on Enter or restart manually the Polyx.

  • Enter the IP-address (see chapter 5.2).

  • Load the Polyx firmware (see chapter 6.1).

  • Load the nodemanager software / security key (see chapter 6.2).

...

9 Technical data

Image RemovedImage Added