Technical Manual | TM-20221022-TV-01

iProtect Access / Security | Integrations | Intrusion Detection |

Image Modified

Installation manuall iProtect → UNii

...

  • Right-click on the virtual line that just is made and select Add node.

  • Enter the following data:
    Name: Enter a logic name
    Type: ‘General intrusion’
    Driver name: ‘Alphavision API driver’
    Communication: UDP (These setting must correspond with the Transmission setting in the UNii, see chapter 2.2)
    Manager code: the manager code of the panel.
    Encryption key: Enter the encryption key which is entered or used in chapter 2.2
    Active: (check)
    Port: Enter the local port number (6502) of the intrusion panel, see chapter 2.2.
    IP-address: enter the IP-address of the intrusion panel

  • Save the data.

  • After a successful connection press on the field Read-in for taking over the programmed configuration from the Alpha-ML UNii panel (groups and points). When the read-in starts or stops, an event will be generated.

...