1. General

The Sirius iX30 -IK IK10 classified IP66 card reader is a versatile card reader which support multiple card technologies and communication protocols used in access control solutions. In addition, the Sirius iX30-IK is able to support different technologies simultaneously.

...

This document assumes standard T-568-B color coding of the cables.

Image Modified

Pin number RJ-45 Plug

TIA/EIA-568-B

Cable color

Signal ID

T568B Pair

1

White/orange

DA+

2

2

Orange

DA-

2

3

White/green

DB+

3

4

Blue

DC+

1

5

White/blue

DC-

1

6

Green

DB+

3

7

White/brown

DD+

4

8

Brown

DD-

4

1.2 Tools and equipment

When installing the Sirius iX30, the following tools or materials may be needed.

...

The following accessories are available for the Sirius iX30-IK

Mounting components

Part number

Mounting screw stainless steel 4,8 x 38 mm

801-5410

Plug Fisher Duopower S6 x 40 mm

801-5411

2. Installation

To ensure proper functioning of the equipment, the environment of the Sirius iX30-IK must be compliant with certain conditions.

...

The configuration defines which card type is read by default by the Sirius IPR-iX30-IKiK10.

Standard communication

RS485 & Clock/Data

RS485 & Clock/Data

-

Read CSN

No

Yes

Functionality

801-5301 TKH coded

801-5302 CSN

801-5303 Programmable

IPR-iX30-iK10-MDF

IPR-iX30-iK10-UID

IPR-iX30-iK10-PRM

Communication

RS485

RS485

RS485

Cosmos Access support

yes

yes

yes

Card data output

Clock/data

Clock/data

-

Output length

8 or 12 digits

10 or 17 digits

-

Read coded TKH cards

Yes

No

-

Output length

8 or 12 digits

10 or 17 digits

Read CSN

No

Yes

-

Reads

programable

Configuration cards

No

No

Yes

Tamper output

Yes

Yes

-

Buzzer input

Yes

Yes

-

LED input

Yes

Yes

-

Default LED

settings

color

Red/Green

Red/Green

Blue

3.1.1

...

IPR-iX30-iK10-MDF

The Sirius iX10 IPR-iX10-MDF can read both TKH coded MIFARE Classic cards and TKH coded Mifare MIFARE DESFire cards simultaneously and works by default at the following devices.

...

Protocol

...

Hardware device (door controller)

...

RS485

...

Orion (stacked)

...

RS485

...

Polyx

...

Clock/Data

...

Orion (KpBus)

...

Clock/Data

...

Orbit

...

Clock/Data

...

Third party devices*

*since clock/data is an standard, the Sirius iX30-IK should work by default on third party controllers which supports the clock/data communication protocol. We strongly recommend to test it on forehand.

3.1.1.1 Output differs per card type

 

TKH Security Mifare Classic:

  • 4 digits system code     e.g.: 1234

  • 4 digits card number     e.g.: 6789

Result as output: 12346789

  

TKH Security Mifare DESFire:

  • 6 digits system code     e.g.: 123456

  • 6 digits card number     e.g.: 789012

Result as output: 123456789012

3.1.2 801-5402 CSN

The Sirius iX30-IK reads both 4 byte and 7 byte CSN simultaneously and works by default at the following devices:

...

Protocol

...

Hardware device (door controller)

...

RS485

...

Orion (stacked)

...

RS485

...

Polyx

...

Clock/Data

...

Orion (KpBus)

...

Clock/Data

...

Orbit*

...

Clock/Data

...

Third party devices**

* 7byte CSN cannot be processed by the Orbit!

** since clock/data is an standard, the Sirius iX30-IK should work by default on third party controllers which supports the clock/data communication protocol. We strongly recommend to test it on forehand.

3.1.2.1 Output differs per card type

 

4Byte CSN:

  • 10 digits CSN

Result as output: 1234567890

 

7Byte CSN:

  • 17 digits CSN  

Result as output: 12345678901234567

3.1.3 801-5403 Programmable

The Sirius iX30-IK 801-5303 programmable does not contain . The table below shows an example of the reader output format.

Example

MIFARE Classic output

MIFARE DESFire output

System code

4 digits: 1234

6 digits: 123456

Card number

4 digits: 6789

6 digits: 789012

Result

12346789

123456789012

3.1.2 IPR-iX30-iK10-UID

The Sirius IPR-iX30-iK10 reads both 4-byte and 7-byte CSN simultaneously. The table below shows an example of the reader output format.

Example

4Byte UID output

7Byte UID output

UID

10 digits

17 digits

Result

123467890

123456789012

3.1.3 IPR-iX30-iK10-PRM

The Sirius iX10 IPR-iX30-iK10 does not have any configuration by default. Programming the Sirius IPR-iX30-IK iK10 depends on the connectioninterface.

Interface / protocol

...

Protocol

...

Hardware device (door controller)

...

How to program

...

RS485

...

Orion (stacked)

...

Reader configuration file

...

RS485

...

Polyx

...

Reader configuration file

...

Clock/Data

...

Orion (KpBus)

...

Configuration card

...

Clock/Data

...

Orbit*

...

Configuration card

...

Clock/Data

...

Third party devices**

...

Configuration card

 Reader configuration file:

A by the Hardware Controll Applet generated reader file which determines the exact configuration. This can be distributed central through iProtect.

  • Create reader configuration file.

  • Upload the file per line.

Detailed information can be found in the manual: TKH Security_HardwareControllApplet.

 

Configuration card:

...

How to program

RS485

Reader configuration file

Clock/data

TKH Security configuration card

3.1.3.1 Configuration card

If the reader is not used with RS485, a configuration card can be used to program the reader to the customer needs. Settings like the default LED color and brightness, Wiegand or Clock/data output and key material can be changed. To program the programmable reader, a customer specific (config) card is needed.
This configuration card can be ordered at TKH Security via cardconfig@tkhsecurity.com.

3.1.3.2 Programming procedure

  • Connect the card reader.

  • Switch on the power. The card readers LED turns into BLUE.

  • Present the configuration card and wait until the card reader restarts.

  • The card readers LED turns into RED. The configuration is complete.

...

The following interfaces are by default available on the Sirius iX30-IK.

...

Label

Interface

Description

A

Light guide

Multicolor RGB LED to display current status

B

Buzzer

Multitone buzzer for audio feedback

C

DIP switch

3-pins DIP switch for RS485 purpose

D

9-Pins connector

Connector to connect card reader to door controller

E

Tamper

Tamper to monitor sabotage

3.4 Connections

...

Pin

description

5-16VDC

Power connection (5-16 Vdc) *

GND

Ground

A

RS485 A

B

RS485 B

LED

Activate LED input

BUZ

Activate Buzzer input

TAMP

Tamper contact

D0

Clock/data- Wiegand, open collector

D1

Clock/data- Wiegand, open collector

* The Sirius iX30-IK accepts a power between 5.0 and 16.0 Vdc. A higher input voltage results in lower power consumption and ensuring cost-efficient wiring with a smaller conductor diameter. When using an external power supply, it must comply with SELV guidelines.

 Advised to power the reader with a power supply that can supply a minimum of 5W to a maximum of 15W. If the reader is powered by a power supply with a power higher than 15W, a fuse of 500mA must be placed by the installer.

DIP SWITCH

Function

1

2

3

Image Modified

DIP-switch 3:
RS485 terminator

DEFAULT

Off

Off

On

Polyx

On

On

Off

Ext.

Off

Off

Off

 3.4.1 RS485 directly

Recommended cable type between the Orion or Polyx and the Sirius iX30-IK card reader is:

...

 If any of the above conditions applies, see chapter 4.4.2.

Image Modified

Pin number RJ-45 Plug

TIA/EIA-568-B

Cable color

Signal

T568B Pair

1

White/orange

B

B

2

Orange

A

A

3

White/green

B

B

4

Blue

VCC

5-16VDC

5

White/blue

-

-

6

Green

A

A

7

White/brown

-

-

8

Brown

GND

GND

...

3.4.2 RS485 via Adapter board

...

 Adapter board is connected with the door controller with a default UTP cat5 cable (or higher) (plug connection).

Or screw connection on adapter board

Or RJ45 connection on adapter board

TIA/EIA-568-B

Cable color

Signal

Sirius iX30-IK

A (or1)

1

White/orange

B

B

B (or 2)

2

Orange

A

A

Y (or 3)

3

White/green

B

B

+

4

Blue

VCC

5-16VDC

 

5

White/blue

 

 

Z (or6)

6

Green

A

A

 

7

White/brown

 

 

-

8

Brown

GND

GND

  • Connect GND of the Adapter board to the local earth.

  • Connect the shield of the ground cable to the GND connection of the Adapter board.

...

  • CKY 3x2x0,14mm²

  • CKY 4x2x0,14mm²

  • CAT5 UTP four twisted pairs of 24AWG copper conductors

  • CAT6 UTP four twisted pairs of 24AWG copper conductors

TIA/EIA-568-B

Cable color

Connection door controller

Sirius iX30-IK

White/orange

Data/D0

D0

Orange

TAMP

TAMP

White/green

Clock/D1        

D1

Blue

VCC (+)

5-16VDC

White/blue

LED

LED

Green

BUZZ

BUZZ

White/brown

GND

GND

Brown

GND

GND

Cable color

Connection door controller

Sirius iX30-IK

Green

Data/D0

D0

Yellow

Clock/D1

D1

Pink

VCC (+)

5-16VDC

Grey

LED

LED

White

GND

GND

Brown

GND

GND

3.4.4 Cable lengths if connected directly to Orion

Cable

Communication protocol

Cable length(m)

Communication between

 

UTP ≥Cat5e   

RS485 Powered from Orion

120

 

Orion and Sirius iX30-IK

card reader

RS485 External powered

600

Wiegand

120

Clock/Data

50

3.4.5 Cable lengths generic

Cable

Communication protocol

Cable length (m)

Communication between

 

 

RS485*

600

 

Controller and Sirius iX30-IK card reader

Wiegand

120

Clock/Data

50

* Please be sure that the cable used for RS485, is suitable for the RS485 protocol.

 Please take into account that the power supply at the reader must be between 5-16 VDC.

...

4.

...

Data signals

...

...

5. Technical specifications

...

Power

supply

Supply voltage

5- 16VDC (max: 1,4W)

Measure

housing

Housing

145 x 82 x 24 mm

PCB

116 x 38 mm

Environment

IP rating

IP66

operating

Operating temp.

-35 … 60ºC

storage

Storage temp.

-40 … 85ºC

interface

Interface

header

Header

9-pins plug connector, small pitch (3.5 / 3.81 mm)

simplex

Simplex
(read only)

Wiegand, open collector

Clock data, open collector

RS485

  • Half duplex, support speeds up to 250Kbps

  • ±2/4/8kV protection airgap discharge

  • ±6 kV contact discharge,

  • ±8 kV using the Human Body Model.

  • Compatible with RS485 standard, Polyx, Orion and Apollo. (Configuration with DIP switches).

Frequencies

13,56MHz

Card detection

2,4GHz band

Wireless connection

Cards

Standard

ISO 14443-A

type

Type

Mifare Classic, Mifare DESFire 0.6, EV1, EV2 and

EV2

EV3

Distance

20-70mm (normal operation)

Main header inputs

LED

With internal pull-up (switch to GND)

(3.3V, <1mA, over voltage protected)

Buzzer

Main header output

Tamper

Open collector without pull-up
(max 500 mA, over voltage protected (Vcc))

Clock/data- Wiegand

User interface

Optic

RGB led / Light guide

sound

Sound

Multi tone buzzer, 85dB at 1 meter

Part number

  • IPR-iX30-iK10-PRM

  • IPR-iX30-iK10-UID

  • IPR-iX30-iK10-MDF

Certification

Electric

EMC / LVD / CE

Radio

R&TTE