*iProtect™ Galaxy
This manual represents the knowledge at the above-mentioned time. TKH security works non-stop to improve her products. For the most recent technical information please contact your consultant or dealer.
1 Introduction
1.1 Sticker i-serie
This manual describes the linking between iProtect and the GalaXy intrusion system.
This document is based on iProtect version 8.00. It is possible that some features cannot be used in older versions of iProtect.
1.2 Required version
Attention: deviations from the specified versions, no guarantee can be given concerning the operation of the link. |
2 Settings GalaXy
2.1 If internal RS232 module
Connect the internal RS232 connection to a network device (iPU-8 (PRT2), Polyx (PRT4) or Pluto using a USB-RS232 converter).
Warning! When a Polyx / iPU-8 is replaced for a Pluto, the connection to the Galaxy panel needs to be changed! |
Note: Maximum cable length is 5m. |
2.2 Programmering interne RS232 module
In the GalaXy center you can program at menu option 56 “Communication” the internal RS232 module.
Choose at menu 56 option 6 (Internal RS232 1). You get a choice out of the next options:
Select option 1: Mode=Direct (press then on <ESC>)
Select option 2: Format=SIA (Set here the desired events which have to be received by iProtect™)
Select option 3: enter the customer number (4 to 6 digits)
Note: If no customer number is entered, no SIA messages will be displayed within iProtect! |
Choose SIA Level= 4 ()
Baud Rate = 38400
Data Bits = 8
Stop Bits = 1
Parity = None
(*) Level 0: (default): Basic event information with 4-digit customer number
Level 1: Equal to Level 0, but with 6-digit customer number
Level 2: Equal to Level 1, but with extra event information
Level 3: Equal to Level 2, but with textual description (highest available level for alarm room)
Level 4: Equal to Level 3, but with addition of commands which can be received by the
GalaXy. This level cannot be used for the Dutch alarm rooms.
After selection of the SIA level, the first trigger will be displayed with the corresponding status (see table underneath). The most messages which can be sent to a receiver by a GalaXy panel are subdivided at the triggers. Use the [A]- or [B]-button or press directly the number for selecting the desired trigger. Press then on the [ent]-button for adapting the settings of this trigger.
Do not the installer menu yet.
2.3 If external RS232 module
Install the GalaXy panel according to the manual. For installer codes etc. see also the corresponding manual.
Unlink temporarily any possible modem/choosers (if version 1.03 or higher).
Connects the iPU-8/Polyx of the iProtect system with the RS232 connector JP2 of the RS232 module of the GalaXy panel. See figure 7 and 8.
Switch on the net voltage of GalaXy panel. Check at ‘DIP’ of the RS232 module the correct settings:
Check the LED’s of the RS232 module. LED2 (red) must burn continuously. LED1 (red) states the communication quality.
2.4 Programming external RS232 module
In the GalaXy panel you can program at menu option 56 “Communication” the external RS232 module.
Choose at menu 56 option 2 (External RS232 module). You get the choice from these options:
Select option 1: Mode=Direct (Press then on <ESC>)
Select option 2: Format=SIA (Set here the desired events which must be received each by iProtect)
Choose SIA Level= 3
Press then a number of times on <ESC> and leave the Master menu. <Again Master code + <ESC>
Select option 3: enter the customer number (4 to 6 digits)
Note! If no customer number is entered, no SIA messages will be displayed within iProtect! |
2.5 Neutralize alarm limitation
(This is valid for internal and external RS232 module.)
Choose at menu 51 option 48. Set the following three options on “0”:
• Number of alarms
• Switch off limit
• Switch on limit
Note! If you do not execute this setting, it can happen that not all alarms will be displayed. |
Exit the installer menu.
3 Settings iProtect
3.1 Add line
For being able to make the correct settings for communication between iProtect and a Galaxy alarm panel, the configuration of the Galaxy panel, which is set by the installer, must exactly be taken over in iProtect.
Click in iProtect on the menu item Installation | Hardware | Line.
Right-click in the browse window and select ‘Add line’. The detail window opens.
Enter the following data:
Name: Type a logical name
Type: ‘Network device’
Host type: Default Pluto but is depending on used hardware
Active: (check)
Active with node’ s: (check)
Mode: ‘Keyprocessor’
IP-address: IP-address of the network deviceSave the data.
3.2 Add node
Click in iProtect on the menu item Installation | Hardware | Node.
Right-click in the browse window and select ‘Add node’. The detail window opens.
Enter the following data:
Name: Specify a logical name
Type: ‘Galaxy ..…..’
Password: Enter the password ‘543210’ < the Remote Service Code of the Galaxy
panel, by default “543210”>
Baudrate: Set to 38400
Address serial port:
iPU-8: scc02:
Polyx: tty02:
Pluto: Pluto external usb #1
Dipswitch 8 (RIO-0): When active RIO 0 will be used (onboard). See chapter 3.2.1
Check ‘Active’.Save the data
3.2.1 Add alarm point
Click in iProtect on the menu item Installation | Hardware | Alarm system | Third Party| Alarm point.
Right-click in the browse window and select ‘Add alarm point’. The detail window opens.
Enter the following data:
Name: Specify a logical name (Copy of the name of the GalaXy alarm point)
Node: Select the node to which this alarm point belongs
Bypassed: No
Enter the number of the alarm pointDipswitch 8 (RIO-0): Check if RIO 0 is used (onboard). The alarm point numbers are:
Save the data
Note! The name of the alarm point needs to be unique in iProtect. Keep in mind when linking multiple GalaXy intrusion systems to iProtect. |
3.2.2 Add alarm group
Click in iProtect on the menu item Installation | Hardware | Alarm system | Third Party| Alarm group.
Right-click in the browse window and select ‘Add alarm group’. The detail window opens.
Enter the following data:
Name: Specify a logical name (Copy of the name of the GalaXy alarm group)
Node: Select the node to which this group belongs
Area: Select an access area. This setting is needed when arming and disarming the (secured)area, using a card reader.
Number: Enter the desired group number.<Block A1=1, A2=2,.. B1=9…
Modus: Select ‘switched off’ at ‘mode’.
Point changes when group off: Select a time zone (example: Office)
< In other words, during which time zone must iProtect monitor the alarm points
for e.g. displaying these statuses on the Keymap>
Write point events to database: Select a time zone (example: Office)
< In other words, during which time zone must iProtect register the alarm points
for e.g. logging these statuses as event and triggering procedures>Save the record.
Right-click in the treeview on the “Alarm group”.
Add alarm point. < Select the earlier created alarm points at the correct alarm group.
Corresponding with the programming in the Galaxy panel >
Note! Using a GalaXy G3 or GD, one alarm point can be linked under multiple alarm groups. |
3.2.3 Add alarm output
Click in iProtect on the menu item Installation | Hardware | Alarm system | Third Party| Alarm output.
Right-click in the browse window and select ‘Add alarm output’. The detail window opens.
Enter the following data:
Name: Specify a logical name (Copy of the name of the GalaXy alarm output)
Node: Select the node to which this alarm output belongs
Mode: Off Output number: Enter the number of the alarm outputTest the connection.
Note! It is possible to control via iProtect outputs of the Galaxy panel. In account has to be taken then that this is not operating in contradiction to the function as given with the Galaxy panel. |
3.2.4 Alarm user Group and admittance
The alarm user Group determines whether the user may arm or disarm the security area.
Open in iProtect the menu item Installation | Hardware | Alarm system | Third party |
Alarm user group. The detail window opens.Enter the following data:
Name: Specify a logical name
Arm: check if allowed to arm the security area
Disarm: check if allowed to disarm the security areaSave the record.
Click in the browse window and click the plus sign of the ‘alarm user group’ and select
'Area list'. Check the desired areas and save.Open in iProtect the menu Access | Settings | Admittance to add the Alarm user group
to an existing AdmittanceSave the record.
3.2.5 Card reader
Open in iProtect the menu item Installation | Hardware | Reader.
Select a card reader which will be used to arm or disarm the security area. The detail window opens.
Open the Tab Security Area:
Show security area status on LED: Select a desired security area
< The LED from the card reader will blink when security area is Armed>
Arm security area: Select a desired security area
Disarm security area: Select a desired security areaOpen the Tab APB:
Select the undefined access area “Outside for access control” at “From area”.
Select the access area you enter at “To area”.Save the record.
4 Visualization alarm system in keymap™
4.1 Placing Widgets
Create under General | Settings | Keymap a floor map.
Click in the frame of the detail window and load a picture of the building or from a floor
where detectors are installed. Save the record. The image will now be displayed as a background image for the alarm visualization.
Loading the background image for the floor map (Dutch working station)
In the treeview underneath the new record of the floor map the record “Widget positioning” has appeared. Click on this record. The detail window ‘Widget positioning’ opens.
By means of Widgets you can now display each sort status of each / each alarm point.
Repeat for each Widget the next steps:
Right-click on the background image and choose ‘Security message (third party)’. Choose ‘alarm point’ and then the sort status, which you want to have displayed. See for this the next chapter about ‘alarm point statuses’.
The default symbol for the momentary status of a default alarm point appears. Drag with the mouse the Widget on the desired place and set the size of the Widget.
Click on the tab sheet ‘Widget control’. Select at ‘column value’ the alarm point, of which the status has to be shown. – You can adapt at ‘column name’ the status once more (you see here a bigger number statuses and parameters from which you can choose). On top of this on the tab sheets you can set or determine the size and position of the Widget exactly, that the status is not displayed with a symbol, but
textual.
Placing Widgets on the background image. In this example three statuses are stated by a symbol (e.g. )
and – on the right - textual (e.g. ‘sabotage closed’).
You can set comparable statuses of alarm groups.
Which default symbols represents which value of a alarm point or alarm group status, can you view at General | Settings | Keymap | Icon assignment.
Open at General | Overviews the new floor map. Check whether changes at the detectors are shown in the right way.
4.2 Alarm point status
You can have 3 sorts status of an alarm point (detector) shown:
• Physical status (or ‘point status’ in the detail window of the alarm point)
• Logical status and
• Calculating status (or ‘alarm status’ in the detail window of the alarm point)
4.2.1 Physical status
The physical status states which resistance the system measures in the detector circuit:
The physical status can be separated thus into 3 groups:
Extreme resistance values which can only be explained by sabotage of the detector (‘Sabotage closed’/ ‘Sabotage opened’), this alarm situation will be notified with the highest priority – independent of e.g. the detector operation
Unusual resistance values which cannot be explained by normal detector operation and e.g. can hint on cable contact (‘Low resistance’/‘High resistance’)
Resistance values, which the detector can assume at regular function (‘Normal’/ ‘Open’)
4.2.2 Logical status
The logical status is a first interpretation of the resistance value based on the sort detector and entered parameters (e.g. ‘bypassed’ on ‘yes’):
Idle: the detector does not notice an insecure situation
Active: the detector notices an insecure situation, but his alarm group does not stand on ‘armed’
Alarm: the detector notices an insecure situation and his alarm group stands on ‘armed’
Bypassed: the messages of this detector will be ignored by the system
Sabotage: e.g. someone opens the housing of the detector without permission
Local alarm
Hold-up alarm
Unknown
4.2.3 Calculated status
The calculated status is a combination of the logical status of the detector and the en de arming of the alarm group of the alarm point:
Idle: the alarm group of the alarm point is not standing anymore on “armed’ and the alarm point does not send an alarm message
Activated: the alarm group of the alarm point stands on “armed’ and the alarm point sends no alarm message
Active: the alarm group of the alarm point does not stand on ‘armed’, the alarm point has passed an alarm message and the alarm group has not been reset
Alarm: the alarm group of the alarm point stands on armed’, the alarm point has passed an alarm message and the alarm group has not been reset
Bypassed: the alarm group of the alarm point stands on ‘bypassed’
5 General
5.1 Type statuses
Physical status (the real loop status)
Open (resistance value)
Closed (resistance value)
Logical status (the translation of the physical status to an alarm situation)
Switched on,
in alarm,
tamper,
etc
Calced status
The translation of [physical + logical] in combination with the (alarm-) status of the group in which the zone sits. At switching off the block the point which has been in alarm, will automatically be reset.
5.2 Maximum number of items in iProtect
The numbers are determined by iProtect. See iProtect; Installation; Database; Table information:
Alarmgroup
Alarmpoint
Alarmgroupalarmpoint
AlarmExternal
5.3 Keymap (Floor plan)
5.4 Event
Go to the menu: General | Settings | Event.
Click in the search window on ‘Search’.
Within iProtect the next event types can be used:
• Alarm point: Status changed
• Alarm point: Bypass status changed
• Alarm point: Mode changed
• Alarm output: Status changed
• Alarm output: Mode changed
• Alarm group: Status changed
• Alarm group: Mode changed
• Alarm group: Alarm changed